E-Zee Flow Heat Exchanger Engineering Data
|
Heat
Exchangers Nominal Performance
|
|
Model
|
Nominal
Capacity
BTU/Hr
|
Hot Water Flow
gpm
|
Pressure Drop
psi
|
Cold Water Flow
gpm
|
Pressure Drop
psi
|
Heater
Transfer
Surface
sq. ft.
|
Weight |
|
EZ-45
|
45.000
|
6.1
|
0.9
|
40
|
1.07
|
1.62
|
4
|
|
EZ-70
|
70.000
|
6.6
|
1.09
|
45
|
1.33
|
2.64
|
6
|
|
EZ-130
|
130.000
|
7.2
|
1.17
|
53
|
1.65
|
3.64
|
10
|
|
EZ-180
|
180.000
|
8
|
0.4
|
55
|
1.1
|
4.70
|
12
|
|
EZ-250
|
250.000
|
9.3
|
0.6
|
71
|
1.7
|
6.80
|
16
|
|
EZ-300
|
300.000
|
10.6
|
0.9
|
80
|
2.5
|
9.00
|
22
|
|
EZ-500
|
500.000
|
14.5
|
1.3
|
95
|
3.2
|
16.80
|
25
|
|
EZ-1000
|
1,000.000
|
25.3
|
2.35
|
186.5
|
4.22
|
21.21
|
39
|

Standard Materials: 316L Stainless Steel
Maximum allowable Working Pressure: 250 psig
Maximum allowable Working Temperature: 406°F
| Dimensions |
| Model |
A |
B |
C |
D |
E |
F |
G |
| EZ-45 |
11
7/8 |
4
13/16 |
5
15/16 |
3
3/16 |
1
1/2 |
1 |
3/4 |
| EZ-70 |
15
7/8 |
9
13/16 |
1
1/2 |
| EZ-130 |
19
3/4 |
11
13/16 |
| EZ-180 |
15
3/16 |
5
9/16 |
10
7/8 |
4 |
1
9/16 |
1 |
| EZ-250 |
20
1/8 |
15
15/16 |
| EZ-300 |
25
7/16 |
21 |
| EZ-500 |
43
9/16 |
39
3/8 |
2
1/4 |
2 |
| EZ-1000 |
38
1/8 |
8
3/4 |
31
1/4 |
5
1/2 |
3
15/16 |
2 |
2 |
Click Below for More Info on Our E-ZEE Flow Heat Exchangers
Sizing Guide -
Engineering Data - Installation Diagram -
Warranty Information |